1. Time measurement: |
12 circuits fixed separating (closing) time separating (closing) inner-phase with asynchronism
Range of internal trigger test: 0.01ms ~ 10s, resolution: 0.01ms,
External trigger test range: 0.01ms ~ 20s, resolution: 0.1ms, |
2. velocity measurement : |
2. velocity measurement : Appointed time slot( stroke segment or angle segment) average velocity |
3. velocity measurement range: |
1mm sensor 0.01~25.00m/s 0.1mm sensor 0.001~2.50m/s 0.5°angle sensor 1 cycle/ 0.5° |
4. Travel measurement: |
Travel of moving contact (travel)
Contact stroke (open distance)
Over travel
Overshoot or rebound stroke
|
5. Measuring range: linear sensor: 50mm, measuring range: |
0-50mm, resolution :0.1mm.
Optional 100-1000mm linear sensor of any length.
Encoder: 360. Rotate sensor, measurement
range: 0-1000mm, resolution :0.25.
|
6.Current resistance range: the maximum current 30 A, resolution: | 0.01 A, 1000 Ω resistance, resolution: 1 Ω. |
7. Instrument power supply: | AC 220V ± 10%; 50 hz plus or minus 2% |
8. Dc power output: | continuously adjustable DC20 ~ 270V, DC110V≤30A (short time), DC220V≤ 20A(short time). Power: 4400W. |
9. External trigger voltage: | AC/DC10-300V, current ≤120A |
10. disconnecting switch measurement range |
(1) Voltage output: DC20~270V(adjustable)
(2) Current output time: 0.01~10 s (settable)
(3) Fracture signal maximum acquisition time: 10s
(4) Measurable fracture closing, separation time, three-phase a synchronism , bounce time and frequency .
|
11. mainframe volume : | 380×280×170mm |
12. operating environment: | -20℃~+50℃ |
13. relative humidity: | ≤80% |